The Honeywell Watchdog III is a flare stack monitoring system that confirms the presence of the flare flame, so that waste gas is burnt rather than released to atmosphere. It pairs a ground-mounted S256BE ultraviolet viewing head with a P222 signal processor, linked by a 50 ft interconnecting cable. The viewing head sees up to 1,000 ft (300 m) line of sight, covering a 40 ft (12 m) target diameter at that distance, and is not affected by sunlight, so it can be sited anywhere around the stack. It works through dust, fog, rain and snow, has no moving parts and can be installed or serviced without shutting down the flare. The processor connects to an existing ignition system, with a flame relay that has an adjustable delay for pilot re-ignition and a separate alarm relay. Outputs include configurable 0-20 or 4-20 mA signals and RS-422/RS-485 Modbus RTU. The viewing head is rated IP66 / NEMA 4X.
| System Type | UV flare stack flame monitoring system |
|---|---|
| Components | S256BE UV viewing head, P222 signal processor, ASY55XBE cable |
| Viewing Distance | Up to 300 m (1,000 ft) line of sight |
| Field of View | 12 m target diameter at 300 m |
| Relay Outputs | R1 DPDT flame relay (0-60 s delay, pilot re-ignition); R2 SPDT alarm (1-3,600 s); 5 A |
| Analog Output | 0-20 mA or 4-20 mA |
| Communications | RS-422/RS-485, Modbus RTU |
| Power | Processor 85-264 VAC or 22-26 VDC; viewing head 24-26 VDC |
| Ingress Protection | IP66 / NEMA 4X (viewing head) |
| Operating Temperature | Processor 0 to 60 °C; viewing head -40 to 80 °C |
| Approvals | CSA 213-M1987, CSA 142-M1987 |
No configuration needed for this product
Price on request
Price on request — a quote will be supplied after review.